윈드터빈 자연환기 장치의 외기풍속 및 온도차에 따른 환기특성에 관한 실험연구An Experimental Study on the Ventilation Characteristics of a Wind-Turbine Natural Ventilator According to the Outdoor-Wind Velocity and the Indoor/Outdoor-Temperature Difference
- Other Titles
- An Experimental Study on the Ventilation Characteristics of a Wind-Turbine Natural Ventilator According to the Outdoor-Wind Velocity and the Indoor/Outdoor-Temperature Difference
- Authors
- 한동훈; 김영식; 정한식; 정효민; 최순호
- Issue Date
- 2017
- Publisher
- 대한설비공학회
- Keywords
- 차압; 자연환기; 온도차; 환기구동력; 풍속; Differential Pressure; Natural Ventilation; Temperature Difference; Ventilation Driving Force; Wind Velocity
- Citation
- 설비공학 논문집, v.29, no.4, pp 175 - 184
- Pages
- 10
- Indexed
- KCI
- Journal Title
- 설비공학 논문집
- Volume
- 29
- Number
- 4
- Start Page
- 175
- End Page
- 184
- URI
- https://scholarworks.gnu.ac.kr/handle/sw.gnu/14637
- DOI
- 10.6110/KJACR.2017.29.4.175
- ISSN
- 1229-6422
2465-7611
- Abstract
- With the improvement of living standards, the ventilation for the mitigation of indoor or outdoor air-pollution problems has recently attracted a lot of attention. Consequently, the ventilation for the supply of outdoor fresh air into a room is treated as an important building-design factor. The ventilation is generally divided into the forced and natural types; here, the former can control the ventilation rate by using mechanical devices, but it has the disadvantages of the equipment costs, maintenance costs, and noise generation, while the latter is applied to most workshops due to the absence of noise and the low installation and maintenance costs. In this experimental study, the ventilation performance of a typical rotating-type natural ventilator, which is called a “wind turbine,” was investigated with the outdoor-wind velocity and the indoor/outdoor-temperature difference. From the experiment results, it was confirmed that the temperature difference of 10℃ corresponds to the ventilation driving force with an outdoor-wind velocity of 1.0 m/s. Additionally, the intake-opening area of a building also exerts a great effect on the ventilation rates.
- Files in This Item