Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Investigation on the Reduction Effect on Cooling Power Consumption and Operating Cost of Mist-spray Outdoor Units in Air ConditionerInvestigation on the Reduction Effect on Cooling Power Consumption and Operating Cost of Mist-spray Outdoor Units in Air Conditioner

Other Titles
Investigation on the Reduction Effect on Cooling Power Consumption and Operating Cost of Mist-spray Outdoor Units in Air Conditioner
Authors
이건호조동우김혜미송영학
Issue Date
2017
Publisher
대한건축학회
Keywords
Mist Spray; Outdoor Unit; Evaporative Cooling; Operating Cost; Cooling Efficiency
Citation
Architectural Research, v.19, no.4, pp 101 - 108
Pages
8
Indexed
KCI
Journal Title
Architectural Research
Volume
19
Number
4
Start Page
101
End Page
108
URI
https://scholarworks.gnu.ac.kr/handle/sw.gnu/14273
DOI
10.5659/AIKAR.2017.19.4.101
ISSN
1229-6163
2383-5575
Abstract
The use of the air conditioner is increasing due to the rise of the outdoor temperature during summer, and the problems of the fire and the cooling performance deterioration are caused due to lack of maintenance of the outdoor unit. In particular, overall performance of cooling system and efficiency in outdoor units have been degraded due to an intake of high-temperature outdoor air thereby increasing cooling energy and operating cost. Thus, this study aimed to increase efficiency of outdoor units by evaporating and cooling intake air through mist spray at the intake port surface in the outdoor unit. The measurements results showed that total power consumption of misting outdoor unit compared to that of conventional outdoor units was reduced by 21% approximately, and total power consumption of the entire system including pump was reduced by 16.7%. In addition, the operating cost including water use was reduced by 13.5% approximately. In summary, if a mist-spray nozzle kit is installed in air-cooled outdoor units, the reduction in the usage of cooling energy and operating cost will be achieved without replacement of existing cooling systems or a large scale of repairs.
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Song, Young Hak photo

Song, Young Hak
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE