Verification of Energy Reduction Effect through Control Optimization of Supply Air Temperature in VRF-OAP Systemopen access

Authors
Lee, Je HyeonYoon, Hyun JinIm, PiljaeSong, Young-hak
Issue Date
Jan-2018
Publisher
MDPI AG
Keywords
variable refrigerant system (VRF); outdoor air processing unit (OAP); control algorithm; experiment; field test; energy savings
Citation
ENERGIES, v.11, no.1
Indexed
SCIE
SCOPUS
Journal Title
ENERGIES
Volume
11
Number
1
URI
https://scholarworks.gnu.ac.kr/handle/sw.gnu/12002
DOI
10.3390/en11010049
ISSN
1996-1073
Abstract
This paper developed an algorithm that controls the supply air temperature in the variable refrigerant flow (VRF), outdoor air processing unit (OAP) system, according to indoor and outdoor temperature and humidity, and verified the effects after applying the algorithm to real buildings. The VRF-OAP system refers to a heating, ventilation, and air conditioning (HVAC) system to complement a ventilation function, which is not provided in the VRF system. It is a system that supplies air indoors by heat treatment of outdoor air through the OAP, as a number of indoor units and OAPs are connected to the outdoor unit in the VRF system simultaneously. This paper conducted experiments with regard to changes in efficiency and the cooling capabilities of each unit and system according to supply air temperature in the OAP using a multicalorimeter. Based on these results, an algorithm that controlled the temperature of the supply air in the OAP was developed considering indoor and outdoor temperatures and humidity. The algorithm was applied in the test building to verify the effects of energy reduction and the effects on indoor temperature and humidity. Loads were changed by adjusting the number of conditioned rooms to verify the effect of the algorithm according to various load conditions. In the field test results, the energy reduction effect was approximately 15-17% at a 100% load, and 4-20% at a 75% load. However, no significant effects were shown at a 50% load. The indoor temperature and humidity reached a comfortable level.
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Song, Young Hak photo

Song, Young Hak
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE