Water-side economizer 시스템의 냉수 및 냉각수 최적 제어를 위한 냉방 에너지 절감 알고리즘 개발Development of Cooling Energy Reduction Algorithm for Optimal Control of Chilled and Condenser Water in WSE

Other Titles
Development of Cooling Energy Reduction Algorithm for Optimal Control of Chilled and Condenser Water in WSE
Authors
고수민김수지송영학
Issue Date
Dec-2025
Publisher
한국건축친환경설비학회
Keywords
Water-side economizer; optimal operation; cooling energy; artificial intelligence; chilled water; condenser water; 외기냉방; 최적 운전; 냉방 에너지; 인공지능; 냉수; 냉각수
Citation
한국건축친환경설비학회 논문집, v.19, no.6, pp 416 - 427
Pages
12
Indexed
KCI
Journal Title
한국건축친환경설비학회 논문집
Volume
19
Number
6
Start Page
416
End Page
427
URI
https://scholarworks.gnu.ac.kr/handle/sw.gnu/81748
ISSN
1976-6483
2586-0666
Abstract
This study aims to develop and quantitatively verify the effectiveness of an optimal control algorithm for a Water-side Economizer (WSE) system to reduce cooling energy consumption in data centers. Optimal fluid combinations that minimize energy usage for each outdoor wet-bulb temperature were derived using a combined LSTM and LightGBM model. An algorithm for the optimal operation of chilled water and condenser 1, 2 water, including the selection of the most appropriate optimal fluid combination, was developed and applied to the WSE system. Comparative analysis between the model with the optimal control algorithm and the Base model revealed that the optimized model enhanced operational stability by precisely and regularly controlling the temperatures of the chilled water and cooling water. Furthermore, the Free cooling operation period increased by approximately 11.8% compared to the conventional operation, while the Chiller cooling operation period decreased by 23.4%, resulting in reduced overall system energy consumption and lowering the peak load from 180 kW to 160 kW. These results confirm that the optimal operation of chilled water and cooling water contributes to cooling energy savings and improved system efficiency in data centers.
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles
공학계열 > 건축공학과 > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Song, Young Hak photo

Song, Young Hak
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE