Markov-Based Reliability Analysis of Hybrid PCS: Evaluation of the Effect of Redundancy Design, PV Generation, and Power Demandopen access
- Authors
- Lim, Seong Jin; Kim, Sun-Pil; Zhou, Guangxu; Kang, Feel-Soon
- Issue Date
- Oct-2025
- Publisher
- Institute of Electrical and Electronics Engineers Inc.
- Keywords
- Energy storage system (ESS); hybrid power conversion system (PCS); hybrid power conversion system (PCS); Markov model; Markov model; mean time to failure (MTTF); mean time to failure (MTTF); photovoltaic; photovoltaic; polymer electrolyte fuel cell (PEMFC); polymer electrolyte fuel cell (PEMFC); redundancy; redundancy; reliability; reliability; reliability
- Citation
- IEEE Access, v.13, pp 174986 - 175009
- Pages
- 24
- Indexed
- SCIE
SCOPUS
- Journal Title
- IEEE Access
- Volume
- 13
- Start Page
- 174986
- End Page
- 175009
- URI
- https://scholarworks.gnu.ac.kr/handle/sw.gnu/80367
- DOI
- 10.1109/ACCESS.2025.3618839
- ISSN
- 2169-3536
2169-3536
- Abstract
- A hybrid power conversion system (PCS) supplies power to the grid using power sources with different characteristics, such as photovoltaic (PV), energy storage system (ESS), and polymer electrolyte fuel cell (PEMFC). If the output of each power source is connected in parallel to the dc-link and a converter with the same power rating is used, a redundancy effect can be obtained. The operation of the hybrid PCS system is determined by the state of charge (SOC) of the ESS battery, and the operating power is determined by the PV generation and grid demand power or ESS battery charging demand power. In this paper, we design a Markov model that considers the reliability of the hybrid PCS by the operating mode, the operating power according to the PV generation and demand power, the operating power change due to partial failure, and the on-load and standby redundancy methods, and analyze the reliability along with the verification of the operation through simulation to present design guidelines for securing high reliability of the hybrid PCS system. The result of the reliability analysis based on an operating temperature of 50 degrees C is that the standby method's lifespan is 9.8% longer than the on-load method. Also, when PV generation exceeds demand power, the average lifespan is 23.4% longer than below the demand. When demand is 3 kW, the lifespan increases by 31.8% compared to 5 kW, and when demand is 1 kW, the lifespan increases by 12.1% compared to 3 kW.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - 공학계열 > 메카트로닉스공학과 > Journal Articles

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.