지역별 기상조건을 고려한 저온 냉각수 온도 및 제조 시간 파악에 관한 연구Verification of Low-temperature Condenser Water and Operation Time considering Climate Zones

Other Titles
Verification of Low-temperature Condenser Water and Operation Time considering Climate Zones
Authors
하주완김유진김환용송영학
Issue Date
2020
Publisher
한국건축친환경설비학회
Keywords
냉각탑; 저온냉각수; 냉각탑 출구온도; 냉각탑제어; 기후 존; Cooling tower; Low-temperature condenser water; Cooling tower leaving water temperature; Cooling tower control; Climate zone
Citation
한국건축친환경설비학회 논문집, v.14, no.3, pp 298 - 309
Pages
12
Indexed
KCI
Journal Title
한국건축친환경설비학회 논문집
Volume
14
Number
3
Start Page
298
End Page
309
URI
https://scholarworks.gnu.ac.kr/handle/sw.gnu/7702
DOI
10.22696/jkiaebs.20200026
ISSN
1976-6483
2586-0666
Abstract
Generally, cooling towers are operated at the nominal value by fixing the condenser water temperature to 32°C. However, it is expected that based on outdoor air, condenser water can be produced at temperatures lower than the nominal value excluding daytime hours in the summer season. On the other hand, from the viewpoint of a refrigeration cycle, the chiller COP increases if the inlet temperature of the condenser is lower. Accordingly, in this study, total amount of time when low-temperature condenser water could be produced, thereby imparting an improvement on the chiller, and assess the condenser water temperature during that time are examined. For calculation, EnergpyPlus v.9.3 was used and the typical meteorological data for Busan, Seoul, Chuncheon, and Daegwallyeong, representing a total of 4 climate zones were applied. In addition, in order to produce low-temperature condenser water, a two-speed control cooling fan and a variable flow-rate pump were adapted. From the result of the simulation, 24 to 27°C condenser water for 77% the cooling system operating time in Busan, and 94% of the cooling system operating time in Seoul was produced, and 21 to 24°C condenser water for 55% of the cooling system operating time in Chuncheon and, 82% of the cooling season operating time in Daegwallyeong was produced. Additionally, during the intermediate season, 24 to 27°C condenser water for 99% of the cooling system operation time in Busan and Seoul was produced, and 21 to 24°C condenser water for 99% and 98% of the cooling system operation time in Chuncheon and Daegwallyeong was produced respectively.
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Kim, Hwan Yong photo

Kim, Hwan Yong
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE