실측을 통한 일개 대학 전산실의 미세먼지 농도특성 분석Field Measurement of Fine Particulate Matter Concentration in a University Computer Room
- Other Titles
- Field Measurement of Fine Particulate Matter Concentration in a University Computer Room
- Authors
- 정창헌
- Issue Date
- 2021
- Publisher
- 한국건축친환경설비학회
- Keywords
- Computer room; Fine particulate matter; I/O ratio; Field measurement; University; 전산실; 미세먼지; 실내외 농도비; 실측; 대학
- Citation
- 한국건축친환경설비학회 논문집, v.15, no.1, pp.19 - 26
- Indexed
- KCI
- Journal Title
- 한국건축친환경설비학회 논문집
- Volume
- 15
- Number
- 1
- Start Page
- 19
- End Page
- 26
- URI
- https://scholarworks.bwise.kr/gnu/handle/sw.gnu/4364
- ISSN
- 1976-6483
- Abstract
- This study determined the concentrations and I/O ratios of fine particulate matter in a computer room located in a university by field measurements. The I/O ratios of fine particulate matters ranged from 0.3 ㎛ to 3.0 ㎛ in computer room, are higher than 1. In addition, concentrations of fine particulate matter at lower part (above 50 cm from floor level) of computer room are higher than upper part (above 100 cm and 150 cm from floor level). These results indicate than computer room needs control over fine particulate matter with smaller diameter (0.3 ㎛ to 3.0 ㎛). Removal of fine particulate matter at lower part of computer room also should be considered to reduce occupants’ health problems.