A Study on the Energy Reduction Measures of Data Centers through Chilled Water Temperature Control and Water-Side Economizeropen access

Authors
Kim, Yu-JinHa, Ju-WanPark, Kyung-SoonSong, Young-Hak
Issue Date
Jun-2021
Publisher
MDPI
Keywords
data center; chilled water temperature; water-side economizer; energy cut-off; HVAC
Citation
ENERGIES, v.14, no.12
Indexed
SCIE
SCOPUS
Journal Title
ENERGIES
Volume
14
Number
12
URI
https://scholarworks.bwise.kr/gnu/handle/sw.gnu/3628
DOI
10.3390/en14123575
ISSN
1996-1073
Abstract
The degree of integration of IT devices and consumption of cooling energy are consistently increasing owing to developments in the data center industry. Hence, to ensure the smooth operation and fault prevention of IT devices, the energy consumption of cooling systems has increased, leading to active research on improvements in cooling system performance for reducing energy consumption. This study examines the reduction in cooling energy consumption using a simulation by applying chilled water control and a water-side economizer (WSE) system to enhance the cooling system efficiency. The simulation results showed that the energy consumption was reduced by 1.8% when the chilled water temperature was set to 11 degrees C in a conventional system and by up to 19.6% when WSE was also applied. Furthermore, when the changes in chilled water temperature were applied for efficient operation of WSE, the energy consumption was reduced by up to 30.1% compared to that in conventional energy systems.
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Song, Young Hak photo

Song, Young Hak
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE