스크린메쉬형 VCHP에서 NCG량에 따른 열전달 성능실험Influence of NCG Charged Mass on the Thermal Performance of VCHP with Screen Mesh Wick

Other Titles
Influence of NCG Charged Mass on the Thermal Performance of VCHP with Screen Mesh Wick
Authors
박영식정경택서정세
Issue Date
2008
Publisher
대한설비공학회
Keywords
Mesh wick(메쉬 윅); Non-condensible gas(불응축 가스); Variable conductance heat pipe(가변전열 히트파이프); Working fluid(작동유체)
Citation
설비공학 논문집, v.20, no.10, pp 689 - 695
Pages
7
Indexed
KCI
Journal Title
설비공학 논문집
Volume
20
Number
10
Start Page
689
End Page
695
URI
https://scholarworks.gnu.ac.kr/handle/sw.gnu/27783
ISSN
1229-6422
2465-7611
Abstract
Experimental study has been performed to investigate the influence of non- condensible gas(NCG) charged mass on the thermal performance of a variable conductance heat pipe(VCHP) with screen mesh wick. The VCHP is furnished by screen mesh number 200 for the pipe outer diameter of 12.7mm and the pipe length of 500mm. The VCHP is filled with water as working fluid of 4.8g and nitrogen as NCG and has evaporator, condenser and adiabatic section, respectively. For the results from experiment, it is found that, for the same charged mass of working fluid, the overall wall temperatures of heat pipe grows up with increasing NCG charged mass. The variation of operating temperature of VCHP reduces with increasing NCG mass. In addition, the profile of axial wall temperature distribution is presented for heat transport capacity of heat pipe, the temperature of cooling water of condenser, inclination angle, and operating temperature.
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > Department of Mechanical Engineering > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Suh, Jeong Se photo

Suh, Jeong Se
공과대학 (기계공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE