실내주차장의 실내공기질 농도특성 및 환기에 의한 저감효과The Effect of Ventilation and Concentration of Indoor Air Quality at Indoor Parking Lots
- Other Titles
- The Effect of Ventilation and Concentration of Indoor Air Quality at Indoor Parking Lots
- Authors
- 박정호
- Issue Date
- 2010
- Publisher
- 한국산업보건학회
- Keywords
- Indoor Air Quality; Indoor Parking Lot; Ventilation; VOCs
- Citation
- 한국산업보건학회지, v.20, no.4, pp 241 - 247
- Pages
- 7
- Indexed
- KCI
- Journal Title
- 한국산업보건학회지
- Volume
- 20
- Number
- 4
- Start Page
- 241
- End Page
- 247
- URI
- https://scholarworks.gnu.ac.kr/handle/sw.gnu/25328
- ISSN
- 2384-132x
2289-0564
- Abstract
- Recently, indoor air quality (IAQ) has been one of the major concerns of people. Indoor parking lots are subject to be exposed to high concentrations of air pollutants emitted from vehicles.
This study was performed to investigate indoor air quality(IAQ) at indoor parking lots. Sampling sites were selected 5 indoor parking lots. Target indoor air quality parameters include a number of criteria pollutants such PM10, CO, CO2, and HCHO.
In addition, a variation of IAQ according to ventilation system operating was measured at C site (underground parking lot).
In general, all pollutants were maintained below indoor air quality maintenance standards. The indoor air quality at indoor parking lots was affected by the availability of the ventilation facility and their operation frequency. At the underground parking lot (C site) with ventilation system, TVOC concentration according to ventilation system operating were found to be lower operating (488.2 μg/m3) than non-operating (1,401.2 μg/m3).
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - 건설환경공과대학 > 환경공학과 > Journal Articles

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.