Cited 0 time in
실내주차장의 실내공기질 농도특성 및 환기에 의한 저감효과
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 박정호 | - |
| dc.date.accessioned | 2022-12-27T04:23:01Z | - |
| dc.date.available | 2022-12-27T04:23:01Z | - |
| dc.date.issued | 2010 | - |
| dc.identifier.issn | 2384-132x | - |
| dc.identifier.issn | 2289-0564 | - |
| dc.identifier.uri | https://scholarworks.gnu.ac.kr/handle/sw.gnu/25328 | - |
| dc.description.abstract | Recently, indoor air quality (IAQ) has been one of the major concerns of people. Indoor parking lots are subject to be exposed to high concentrations of air pollutants emitted from vehicles. This study was performed to investigate indoor air quality(IAQ) at indoor parking lots. Sampling sites were selected 5 indoor parking lots. Target indoor air quality parameters include a number of criteria pollutants such PM10, CO, CO2, and HCHO. In addition, a variation of IAQ according to ventilation system operating was measured at C site (underground parking lot). In general, all pollutants were maintained below indoor air quality maintenance standards. The indoor air quality at indoor parking lots was affected by the availability of the ventilation facility and their operation frequency. At the underground parking lot (C site) with ventilation system, TVOC concentration according to ventilation system operating were found to be lower operating (488.2 μg/m3) than non-operating (1,401.2 μg/m3). | - |
| dc.format.extent | 7 | - |
| dc.language | 한국어 | - |
| dc.language.iso | KOR | - |
| dc.publisher | 한국산업보건학회 | - |
| dc.title | 실내주차장의 실내공기질 농도특성 및 환기에 의한 저감효과 | - |
| dc.title.alternative | The Effect of Ventilation and Concentration of Indoor Air Quality at Indoor Parking Lots | - |
| dc.type | Article | - |
| dc.publisher.location | 대한민국 | - |
| dc.identifier.bibliographicCitation | 한국산업보건학회지, v.20, no.4, pp 241 - 247 | - |
| dc.citation.title | 한국산업보건학회지 | - |
| dc.citation.volume | 20 | - |
| dc.citation.number | 4 | - |
| dc.citation.startPage | 241 | - |
| dc.citation.endPage | 247 | - |
| dc.identifier.kciid | ART001510726 | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | kci | - |
| dc.subject.keywordAuthor | Indoor Air Quality | - |
| dc.subject.keywordAuthor | Indoor Parking Lot | - |
| dc.subject.keywordAuthor | Ventilation | - |
| dc.subject.keywordAuthor | VOCs | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
Gyeongsang National University Central Library, 501, Jinju-daero, Jinju-si, Gyeongsangnam-do, 52828, Republic of Korea+82-55-772-0532
COPYRIGHT 2022 GYEONGSANG NATIONAL UNIVERSITY LIBRARY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.
