Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

바닥 복사난방 배관설비에서 배관파열 사례 연구open accessA Case Study on the Plumbing Pipe Burst of Floor Radiant Heating

Other Titles
A Case Study on the Plumbing Pipe Burst of Floor Radiant Heating
Authors
정홍도신용한박진관정효민정한식
Issue Date
2012
Publisher
대한설비공학회
Keywords
Ondol(온돌); Floor radiant heating(바닥복사난방); Thermostat(온도조절기); Tensile strength(인장강도)
Citation
설비공학 논문집, v.24, no.10, pp 745 - 749
Pages
5
Indexed
KCI
Journal Title
설비공학 논문집
Volume
24
Number
10
Start Page
745
End Page
749
URI
https://scholarworks.gnu.ac.kr/handle/sw.gnu/22784
DOI
10.6110/KJACR.2012.24.10.745
ISSN
1229-6422
2465-7611
Abstract
Heating pipes burst was occurred in the apartment complex that was applied floor radiant heating system. There were two opinions for the cause of the bursted heating pipes that was the flaw during construction and defects in the product and also there were conflicting among them. Officials analyzed it in order to investigate the cause of the rupture. Tensile test results showed different tensile strength between the lower part of heating pipe and the upper part of heating pipes. The lower tensile strength is maintained while the top was not secured. The reason why rupture heating pipes is that flow velocity isn’t secured and then the air get stagnant. Stagnant air makes hardening. It is caused rupturing. The proper flow rate was confirmed 0.166 m/sec after experiment. It isn’t make stagnant air inside heating pipes.
Files in This Item
There are no files associated with this item.
Appears in
Collections
해양과학대학 > ETC > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE