바닥 복사난방 배관설비에서 배관파열 사례 연구open accessA Case Study on the Plumbing Pipe Burst of Floor Radiant Heating
- Other Titles
- A Case Study on the Plumbing Pipe Burst of Floor Radiant Heating
- Authors
- 정홍도; 신용한; 박진관; 정효민; 정한식
- Issue Date
- 2012
- Publisher
- 대한설비공학회
- Keywords
- Ondol(온돌); Floor radiant heating(바닥복사난방); Thermostat(온도조절기); Tensile strength(인장강도)
- Citation
- 설비공학 논문집, v.24, no.10, pp 745 - 749
- Pages
- 5
- Indexed
- KCI
- Journal Title
- 설비공학 논문집
- Volume
- 24
- Number
- 10
- Start Page
- 745
- End Page
- 749
- URI
- https://scholarworks.gnu.ac.kr/handle/sw.gnu/22784
- DOI
- 10.6110/KJACR.2012.24.10.745
- ISSN
- 1229-6422
2465-7611
- Abstract
- Heating pipes burst was occurred in the apartment complex that was applied floor radiant heating system. There were two opinions for the cause of the bursted heating pipes that was the flaw during construction and defects in the product and also there were conflicting among them. Officials analyzed it in order to investigate the cause of the rupture. Tensile test results showed different tensile strength between the lower part of heating pipe and the upper part of heating pipes. The lower tensile strength is maintained while the top was not secured. The reason why rupture heating pipes is that flow velocity isn’t secured and then the air get stagnant. Stagnant air makes hardening. It is caused rupturing. The proper flow rate was confirmed 0.166 m/sec after experiment. It isn’t make stagnant air inside heating pipes.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - 해양과학대학 > ETC > Journal Articles

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.