Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

BEMS 데이터를 활용한 도서관 건물의 운전현황 분석 -준공 초기단계의 건물 에너지 성능 평가-An Operation Status Analysis of Library Building using BEMS Data; Energy Performance Evaluation on Initial Stage of Completion

Other Titles
An Operation Status Analysis of Library Building using BEMS Data; Energy Performance Evaluation on Initial Stage of Completion
Authors
박성철하주완김환용송영학
Issue Date
2018
Publisher
한국건축친환경설비학회
Keywords
BEMS (BuildingEnergyManagementSystem); Measured Data; Geothermal System; Heat Storage System; Operation Status Analysis; BEMS; 실측데이터; 지열시스템; 축열시스템; 운전현황 분석
Citation
한국건축친환경설비학회 논문집, v.12, no.6, pp 669 - 679
Pages
11
Indexed
KCI
Journal Title
한국건축친환경설비학회 논문집
Volume
12
Number
6
Start Page
669
End Page
679
URI
https://scholarworks.gnu.ac.kr/handle/sw.gnu/12396
DOI
10.22696/jkiaebs.20180055
ISSN
1976-6483
2586-0666
Abstract
Energy consumption savings in buildings should be reviewed in diverse areas such as air conditioning system and lighting responsible for cooling and heating, and energy management systems such as BAS (Building Automation System) and BEMS (Building Energy Management System) are introduced to improve energy consumption efficiency and to promote economic control of related facilities by integrated management of energy generated and consumption in buildings. The measured building of this study uses regenerative geothermal system. Measured values of heat pump and system COP were 4.7 and 4.2 respectively, and they were found to be higher 11.9% and 23.5% than rated values. As a result of analyzing the air conditioning and lighting energy from the first floor to the fourth floor performing the air conditioning, the second and third floors, which have a high frequency of use, are compared with the first and fourth floors 50% higher energy consumption ratio. On the other hand, the general heat storage system uses the nighttime power of the previous day to store heat and use it the next day. The total number of days of abnormal operation during the summer season is 61 days. The electricity cost corresponding to the abnormal operation is 1,840,641 KRW, and the normal operation using the nighttime power is 1,363,561 KRW, which is difference of 477,080 KRW, 35% increase in cost. We will utilize it as the main data of BEMS through analysis of winter operation characteristics as well as summer operation characteristics.
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Kim, Hwan Yong photo

Kim, Hwan Yong
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE