Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

BEMS 데이터를 활용한 축열 시스템의 운전 성능 및 효율 저하 평가에 관한 연구An Evaluation on the Operation Performance and Reduced Efficiency of Thermal Storage System via BEMS Data

Other Titles
An Evaluation on the Operation Performance and Reduced Efficiency of Thermal Storage System via BEMS Data
Authors
박성철김유진김환용송영학
Issue Date
2019
Publisher
한국건축친환경설비학회
Keywords
Thermal Storage System; BEMS; Geothermal Heat Pump; Design Error; Operation Efficiency; 축열시스템; BEMS; 지열히트펌프; 설계오류; 운전효율
Citation
한국건축친환경설비학회 논문집, v.13, no.6, pp 481 - 490
Pages
10
Indexed
KCI
Journal Title
한국건축친환경설비학회 논문집
Volume
13
Number
6
Start Page
481
End Page
490
URI
https://scholarworks.gnu.ac.kr/handle/sw.gnu/10017
DOI
10.22696/jkiaebs.20190041
ISSN
1976-6483
2586-0666
Abstract
This study summarized and analyzed the operation status of heating, ventilation, and air conditioning (HVAC) in buildings using the data acquired by a building energy management system (BEMS) and identified the operation performance. The target building was a library where energy efficiency grade, passive buildings, and passive and active elements were applied such as Grade 5 zero energy building (ZEB). The main components of the HVAC system was composed of thermal storage tank system utilizing the mid-night electric power and geothermal heat pump. The analysis results verified that the mean Coefficient of Performances (COP) of the heat pump device and the system during heating operation were 3.7 and 3.2, which were decreased in operating efficiency by -2.9% and -4.5%, and 4.5 and 3.4 during cooling operation, which were improved in operating efficiency by 5.7% and -5.0%. In the middle of the process that checked the loss of heat storage during cooling operation, the design errors occurred in the pipe system in the thermal storage tank were verified. The temperature stratification inside the thermal storage system was not made because the 3-way valve was not implemented in the sections of the heat pump and thermal storage tank. The comparison results based on the assumption of normal design showed that the heat storage loss for 22 days in a month of July in 2019 was 31,228 kWh. Considering the daily loss and system COP, the entire power loss of heat storage in July was 9,281 kWh, which incurred additional cost of KRW 514,161 accordingly.
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Kim, Hwan Yong photo

Kim, Hwan Yong
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE