상세 보기
- 박병용;
- 정창헌;
- 신철웅;
- 류성용
WEB OF SCIENCE
0SCOPUS
0초록
Purpose: Recently, owing to the high concentration of fine dust, air filters have become essential in heat-recovery ventilators. In Korea, air filter performance is evaluated by the standard, “KS B 6141 Air Filter Units for Ventilation.” However, filter lifetime has not been examined. In this study, an accelerated test method for air filters was developed. In addition, the change in the supply air flow rate was analyzed under filter conditions. Method: The filter accelerated test conditions were identified, and the annual average concentration of fine dust in the atmosphere was determined. A vertical wind tunnel was built to evaluate the air filter lifetime. The ISO A2 dust was dosed to an air filter. In addition, the supply air flow rates were measured for the three products that the accelerated air filter used. Result: Under the lab test conditions, the supply air flow rate changed with the filter usage time and the air resistance. In the experiments, only ISO A2 dust was used. Subsequently, the effects of various particles were tested on the development of the acceleration test method for filters.
키워드
- 제목
- Analysis of Air Supply Air Flow Rate Decrease by Accelerated Dust Load Experiments on Heat-Recovery Ventilator Air Filter
- 제목 (타언어)
- Analysis of Air Supply Air Flow Rate Decrease by Accelerated Dust Load Experiments on Heat-Recovery Ventilator Air Filter
- 저자
- 박병용; 정창헌; 신철웅; 류성용
- 발행일
- 2022-12
- 저널명
- KIEAE Journal
- 권
- 22
- 호
- 6
- 페이지
- 15 ~ 20