데이터센터 에너지 예측 모델을 활용한 외기습구온도별 최적 유체 온도 도출에 대한 연구
A Study on the Derivation of Optimal Fluid Temperature by Outdoor Wet-bulb using Energy Predicted Model in Data Center

초록

As societal demands for carbon neutrality continue to rise, reducing energy consumption in the building sector has become essential. Among various building types, data centers consume a significant amount of energy, prompting numerous studies to explore the application of Water-side Economizer (WSE) systems that enable Free Cooling operation for enhanced energy efficiency. This study aims to optimize the performance of WSE systems by proposing a control strategy that minimizes cooling energy consumption in response to varying outdoor conditions. As a preliminary step, a cooling energy prediction model for a data center was developed to derive optimal fluid temperature setpoints that minimize energy usage according to outdoor wet-bulb temperature. The predictive model was constructed using Long Short-Term Memory (LSTM) and Light Gradient Boosting Machine (LightGBM), and demonstrated high accuracy and reliability with R-squared value of 0.995, CV (RMSE) of 4.31%, and an MAE of approximately 1.13 kW. Based on this model, optimal fluid temperature combinations were determined for each outdoor wet-bulb condition throughout the year. These results are expected to serve as a foundational guideline for developing future control algorithms and establishing energy-efficient operation strategies.

키워드

냉방 에너지예측 모델유체 온도외기습구온도외기냉수냉방Artificial Intelligence (AI)Predicted modelOutdoor humidity temperatureChilledwaterCondenser water
제목
데이터센터 에너지 예측 모델을 활용한 외기습구온도별 최적 유체 온도 도출에 대한 연구
제목 (타언어)
A Study on the Derivation of Optimal Fluid Temperature by Outdoor Wet-bulb using Energy Predicted Model in Data Center
저자
고수민송영학
발행일
2025-10
유형
Y
저널명
한국건축친환경설비학회 논문집
19
5
페이지
191 ~ 200