Parametric Study on Water Mist Nozzles for Fire Suppression System Based on CFD Methods

Parametric Study on Water Mist Nozzles for Fire Suppression System Based on CFD Methods
  • 정인수; 
  • 박태규; 
  • 정희택

초록

Numerical simulation has been performed to investigate the mist flow characteristics through the fire suppression nozzles for the design purposes. The commercial softwares, FLUENT and the fire dynamic simulator, FDS with the proper modelings were chosen as the numerical tools. In order to find optimal conditions in sense of the main performances of nozzles, the spray characteristics were analyzed both inside and outside of the nozzles. Geometric factors of the injecting orifices, i.e., diameter and chamfered angle were chosen as the simulation parameters for design application. From the present numerical results, 1.0c nozzles, whose orifice-diameter was 1 mm, having the chamfered angles were shown as the best performance of the fire suppression.

키워드

Water mist; Fire suppression nozzle; Spray characteristics; CFD; Design parameters; Performance
제목
Parametric Study on Water Mist Nozzles for Fire Suppression System Based on CFD Methods
제목 (타언어)
Parametric Study on Water Mist Nozzles for Fire Suppression System Based on CFD Methods
저자
정인수; 박태규; 정희택
발행일
2010
저널명
한국액체미립화 학회지
권
15
호
3
페이지
124 ~ 130