미분무 시스템이 장착된 화염방지장치의 화재 진화 특성에 관한 연구

A Study on the Fire Suppression Characteristics of a Flame Arrester with Water Mist System

초록

In this paper, we developed a breather valve with a water mist system for use near an oil storage tank. Ourprocess applied a water mist system to the flame arrester to evaluate the fire suppression characteristics. For thefire suppression evaluation of the water mist system, we evaluated the angle of the nozzle, fire suppression,spray particle size, flashback, fire suppression time, and fire suppression test of antifreeze. Through the firesuppression test, the best fire suppression nozzle used an angle of 140 °, and the flashback phenomenon offlame arrester did not occur. The fire suppression time of water mist system time was within three seconds, andthe antifreeze was no problem with the fire suppression.

키워드

Flame Arrester(화염방지장치); Water Mist System(미분무시스템); Fire Suppression(화재진화)
제목
미분무 시스템이 장착된 화염방지장치의 화재 진화 특성에 관한 연구
제목 (타언어)
A Study on the Fire Suppression Characteristics of a Flame Arrester with Water Mist System
저자
김해지; 이경로
DOI
10.14775/ksmpe.2016.15.5.117
발행일
2016
저널명
한국기계가공학회지
권
15
호
5
페이지
117 ~ 124