데이터센터의 Water-Side Economizer 시스템 Free Cooling 운전 모드에 따른 에너지 효율 검토
Energy Efficiency Analysis on Free Cooling Operation Mode of the Water-Side Economizer System in Data Center

초록

Water-side economizer (WSE) systems are being introduced to reduce cooling energy in data centers, but quantitative comparisons of various controls are impossible as the configurations of the systems are different. Therefore, this study reviewed the energy consumption according to the free cooling operation mode of the WSE system, and analyzed the operation status according to the South Korea climate zone to reduce additional energy and secure free cooling operation time. In the case of a WSE system that can only operate full-free cooling, about 10.9% of energy was saved. When full and partial-free cooling operations were implemented through th serial connection between the chiller and the heat exchanger, 13.7% of energy was saved. In particular, Daegwallyeong (6A), located in the climate zone with the lowest ambient air humidity temperature, Showed the highest energy savings of about 19.5% compared to the center chilled water system as free cooling operating time was secured the most.

키워드

데이터센터외기냉수냉방프리쿨링기후존에너지 사용량Data centerWater-side economizerFree coolingClimate zoneEnergy consumption
제목
데이터센터의 Water-Side Economizer 시스템 Free Cooling 운전 모드에 따른 에너지 효율 검토
제목 (타언어)
Energy Efficiency Analysis on Free Cooling Operation Mode of the Water-Side Economizer System in Data Center
저자
김유진하주완임완욱김환용송영학
DOI
10.22696/jkiaebs.20220001
발행일
2022-02
저널명
한국건축친환경설비학회 논문집
16
1
페이지
1 ~ 13