상세 보기
초록
Control valves are final control elements in power plants, but closed-loop compensation can obscure early valvecondition changes in alarms and operating trends. This study proposes an operating-region-based ConditionalMasking Index (CMI) using Distributed Control System (DCS) and historian data without additional sensors. Comparableload and valve-opening regions were selected, and physical indicators were scored using reference-periodquantiles and integrated into a 0~100 CMI. In the low-load region, the median CMI increased from 1.22 to 83.20in Unit #1 and from 2.30 to 81.82 in Unit #2, temporally consistent with positioner adjustment and inspectionrecords. In the high-load region, CMI remained near 20. The results show that CMI can quantify condition changesmasked by closed-loop control and support maintenance review
키워드
- 제목
- 발전소 고압드럼 수위조절밸브 상태감시를 위한 운전영역기반 조건부 마스킹지수 산정에 관한 연구
- 제목 (타언어)
- Operating-Region-Based Conditional Masking Index for Condition Monitoring of a High-Pressure Drum Level Control Valve in a Power Plant
- 저자
- 신현식; 이순영; 김태형
- 발행일
- 2026-09
- 유형
- Y
- 저널명
- 전기전자학회논문지
- 권
- 30
- 호
- 3
- 페이지
- 408 ~ 417
- 언어
- KOR
- 출판사
- 한국전기전자학회
- 발행국가
- 대한민국
- 분량
- 10 페이지
- ISSN
- E 2288-243X
P 1226-7244