모듈 타입별 음압병실의 기류해석을 통한 격리성능 검토 연구
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 박형은 | - |
| dc.contributor.author | 송영학 | - |
| dc.date.accessioned | 2023-11-13T07:42:54Z | - |
| dc.date.available | 2023-11-13T07:42:54Z | - |
| dc.date.issued | 2023-10 | - |
| dc.identifier.issn | 1976-6483 | - |
| dc.identifier.issn | 2586-0666 | - |
| dc.identifier.uri | https://scholarworks.gnu.ac.kr/handle/sw.gnu/68463 | - |
| dc.description.abstract | In this study, a preliminary review was conducted on the module type and problem-causing factors of the infill-type modular negative pressure field. Through CFD analysis, isolation performance for various ward types was quantitatively reviewed and the impact of contaminated air on adjacent room was identified. Due to the highly variable nature of the infill method, single-person room and double-person room were divided into unit modules to examine indoor airflow and inter-space pressure differential, and then a combination module was constructed by adjacent unit modules, and the degree of contaminated air leakage was analyzed depending on whether the interlock was open or not. The simulation results, during normal operation of each unit module, the pressure distribution appears in the following order : clean corridor> anteroom > contaminated corridor> isolation room> toilet. On the other hand, during abnormal operation due to interlock opening, it was confirmed that the isolation room (IR) and space outside the IR momentarily took the form of equal pressure and air leaked | - |
| dc.format.extent | 12 | - |
| dc.language | 한국어 | - |
| dc.language.iso | KOR | - |
| dc.publisher | 한국건축친환경설비학회 | - |
| dc.title | 모듈 타입별 음압병실의 기류해석을 통한 격리성능 검토 연구 | - |
| dc.title.alternative | A Study on the Isolation Performance of Modular Negative Pressure Room by Air Flow Analysis | - |
| dc.type | Article | - |
| dc.publisher.location | 대한민국 | - |
| dc.identifier.bibliographicCitation | 한국건축친환경설비학회 논문집, v.17, no.5, pp 284 - 295 | - |
| dc.citation.title | 한국건축친환경설비학회 논문집 | - |
| dc.citation.volume | 17 | - |
| dc.citation.number | 5 | - |
| dc.citation.startPage | 284 | - |
| dc.citation.endPage | 295 | - |
| dc.identifier.kciid | ART003011455 | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | kci | - |
| dc.subject.keywordAuthor | Negative pressure isolation room | - |
| dc.subject.keywordAuthor | CFD analysis | - |
| dc.subject.keywordAuthor | Ventilation system | - |
| dc.subject.keywordAuthor | Module type | - |
| dc.subject.keywordAuthor | Operation scenario | - |
| dc.subject.keywordAuthor | 음압격리병실 | - |
| dc.subject.keywordAuthor | CFD 해석 | - |
| dc.subject.keywordAuthor | 환기 시스템 | - |
| dc.subject.keywordAuthor | 모듈 타입 | - |
| dc.subject.keywordAuthor | 운영 시나리오 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
Gyeongsang National University Central Library, 501, Jinju-daero, Jinju-si, Gyeongsangnam-do, 52828, Republic of Korea+82-55-772-0532
COPYRIGHT 2022 GYEONGSANG NATIONAL UNIVERSITY LIBRARY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.