축열조 연동 Water-side Economizer 시스템의 동계 냉방 에너지 및 비용 절감 효용에 관한 연구A Study on the Effectiveness of Cooling Energy and Cost Reduction in Thermal Energy Storage with Water-side Economizer

Other Titles
A Study on the Effectiveness of Cooling Energy and Cost Reduction in Thermal Energy Storage with Water-side Economizer
Authors
임완욱김유진송영학
Issue Date
Oct-2022
Publisher
한국건축친환경설비학회
Keywords
24 h 냉방운전; 에너지 소비량; 운전 비용; 축열조; 프리쿨링 시스템; 디자인빌더; 24 h cooling operation; Energy consumption; Operating cost; Thermal energy storage; Free cooling System; DesignBuilder
Citation
한국건축친환경설비학회 논문집, v.16, no.5, pp 346 - 358
Pages
13
Indexed
KCI
Journal Title
한국건축친환경설비학회 논문집
Volume
16
Number
5
Start Page
346
End Page
358
URI
https://scholarworks.gnu.ac.kr/handle/sw.gnu/29848
ISSN
1976-6483
2586-0666
Abstract
Air conditioning energy accounts for more than 50% of the total energy used in buildings. Recently, in general office buildings the cooling load of winter is increasing as it has a server room by establishing its own computer system for the purpose of managing computer and data and strengthening security. As the cooling load of winter increases, a study combining a TES (thermal energy storage) system that reduces operation costs by transferring power demand to late-night hours and a free-cooling system that reduces cooling energy consumption by using low-temperature outdoor air under conditions below a specific temperature is in progress. Therefore, this study intends to deepen the study by focusing on previous studies that implement a complementary model of each system for a building that is subjected to a 24-hour cooling load even in winter. By using DesignBuilder, a dynamic simulation program, cold water produced through WSE is used for 4 months during the winter (December to March) when the outside temperature is low to remove the load occurring at night. At the same time, in this study intend to implement a TES-linked free-cooling system that stores cold water in the TES and discharges heat during the next daytime, and the system will be referred to as a “Combination model”. Buildings and equipment were modeled with reference to ASHRAE standards and guidelines. For the target building, energy consumption and cost savings of cooling operation were reviewed using standard meteorological data of Seoul, and heating operation was excluded from the simulation model. As a result of analyzing the simulation, it was confirmed that the combined model reduced energy consumption by 27% and operating cost by 51% compared to the conventional method.
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles
공학계열 > 건축공학과 > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Song, Young Hak photo

Song, Young Hak
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE