태안 시설원예단지의 온실 냉난방 부하 분석Analyses of Heating and Cooling load in Greenhouse of Protected Horticulture Complex in Taean
- Other Titles
- Analyses of Heating and Cooling load in Greenhouse of Protected Horticulture Complex in Taean
- Authors
- 서원명; 배용한; 허해준; 곽철순; 이석건; 이종원; 윤용철
- Issue Date
- 2009
- Publisher
- 한국농공학회
- Keywords
- Heating and cooling load; amount of ventilation; flat plate solar collector; geothermal heat pump; KSU-greenhouse model; economic analyses; venlo type greenhouse
economic analyses; venlo type greenhouse
- Citation
- 한국농공학회논문집, v.51, no.6, pp 45 - 52
- Pages
- 8
- Indexed
- KCI
- Journal Title
- 한국농공학회논문집
- Volume
- 51
- Number
- 6
- Start Page
- 45
- End Page
- 52
- URI
- https://scholarworks.gnu.ac.kr/handle/sw.gnu/26658
- ISSN
- 1738-3692
2093-7709
- Abstract
- This study was conducted in the process that the basic plan of the formation of the thermal energy complex in the Iwon reclaimed land of Taean was being made. Targeting for the large-sized greenhouse to be made in this area, it examined the cooling and heating load and the amount of ventilation, and also analyzed the economic efficiency of heating. The research results are as
per the below: The minimum ambient temperature of this area was measured on January 7, 2001, which was -18.7 ℃, and the maximum ambient temperature of this area was measured on July 24, 1994, which was 36.7 ℃. The maximum heating load was 39,011 MJ/h, but the date when the maximum heating load was not consistent with the date when the minimum temperature was measured. The maximum cooling load was 88,562MJ/h, It was approximately 2.3 times of the maximum heating load, which was measured at 14:00 hours on September 4, 2000. The maximum amount of ventilation heat was 138,639MJ/h. Assuming the rate of solar heat use as 10 %, 20 %, 50 %, and 100 %, the total sum of cost-benefit would be ₩-193,450,000, ₩-634,930,000, ₩-3,372,960,000, and ₩-9,850,420,000, respectively 20 years later. The break-even point of the geothermal heat pump would be about 4 years for 10 % use, about 3 years for 20 % or 50% use, and approximately 6 years for 100% use. It was found that 50 % use would be most advantageous. In case two systems are combined, the break-even point will be 10 years, 8 years, and 11years respectively.