Parametric Study on Water Mist Nozzles for Fire Suppression System Based on CFD MethodsParametric Study on Water Mist Nozzles for Fire Suppression System Based on CFD Methods
- Other Titles
- Parametric Study on Water Mist Nozzles for Fire Suppression System Based on CFD Methods
- Authors
- 정인수; 박태규; 정희택
- Issue Date
- 2010
- Publisher
- 한국분무공학회
- Keywords
- Water mist; Fire suppression nozzle; Spray characteristics; CFD; Design parameters; Performance
- Citation
- 한국분무공학회지, v.15, no.3, pp 124 - 130
- Pages
- 7
- Indexed
- KCI
- Journal Title
- 한국분무공학회지
- Volume
- 15
- Number
- 3
- Start Page
- 124
- End Page
- 130
- URI
- https://scholarworks.gnu.ac.kr/handle/sw.gnu/25623
- ISSN
- 1226-2277
- Abstract
- Numerical simulation has been performed to investigate the mist flow characteristics through the fire suppression nozzles for the design purposes. The commercial softwares, FLUENT and the fire dynamic simulator, FDS with the proper modelings were chosen as the numerical tools. In order to find optimal conditions in sense of the main performances of nozzles, the spray characteristics were analyzed both inside and outside of the nozzles. Geometric factors of the injecting orifices, i.e., diameter and chamfered angle were chosen as the simulation parameters for design application. From the present numerical results, 1.0c nozzles, whose orifice-diameter was 1 mm, having the chamfered angles were shown as the best performance of the fire suppression.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - 공과대학 > Department of Mechanical Engineering > Journal Articles

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.