Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

데이터센터의 Water-Side Economizer 시스템 Free Cooling 운전 모드에 따른 에너지 효율 검토

Full metadata record
DC Field Value Language
dc.contributor.author김유진-
dc.contributor.author하주완-
dc.contributor.author임완욱-
dc.contributor.author김환용-
dc.contributor.author송영학-
dc.date.accessioned2022-12-26T09:21:15Z-
dc.date.available2022-12-26T09:21:15Z-
dc.date.issued2022-02-
dc.identifier.issn1976-6483-
dc.identifier.issn2586-0666-
dc.identifier.urihttps://scholarworks.gnu.ac.kr/handle/sw.gnu/2534-
dc.description.abstractWater-side economizer (WSE) systems are being introduced to reduce cooling energy in data centers, but quantitative comparisons of various controls are impossible as the configurations of the systems are different. Therefore, this study reviewed the energy consumption according to the free cooling operation mode of the WSE system, and analyzed the operation status according to the South Korea climate zone to reduce additional energy and secure free cooling operation time. In the case of a WSE system that can only operate full-free cooling, about 10.9% of energy was saved. When full and partial-free cooling operations were implemented through th serial connection between the chiller and the heat exchanger, 13.7% of energy was saved. In particular, Daegwallyeong (6A), located in the climate zone with the lowest ambient air humidity temperature, Showed the highest energy savings of about 19.5% compared to the center chilled water system as free cooling operating time was secured the most.-
dc.format.extent13-
dc.language한국어-
dc.language.isoKOR-
dc.publisher한국건축친환경설비학회-
dc.title데이터센터의 Water-Side Economizer 시스템 Free Cooling 운전 모드에 따른 에너지 효율 검토-
dc.title.alternativeEnergy Efficiency Analysis on Free Cooling Operation Mode of the Water-Side Economizer System in Data Center-
dc.typeArticle-
dc.publisher.location대한민국-
dc.identifier.doi10.22696/jkiaebs.20220001-
dc.identifier.bibliographicCitation한국건축친환경설비학회 논문집, v.16, no.1, pp 1 - 13-
dc.citation.title한국건축친환경설비학회 논문집-
dc.citation.volume16-
dc.citation.number1-
dc.citation.startPage1-
dc.citation.endPage13-
dc.identifier.kciidART002813683-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClasskci-
dc.subject.keywordAuthor데이터센터-
dc.subject.keywordAuthor외기냉수냉방-
dc.subject.keywordAuthor프리쿨링-
dc.subject.keywordAuthor기후존-
dc.subject.keywordAuthor에너지 사용량-
dc.subject.keywordAuthorData center-
dc.subject.keywordAuthorWater-side economizer-
dc.subject.keywordAuthorFree cooling-
dc.subject.keywordAuthorClimate zone-
dc.subject.keywordAuthorEnergy consumption-
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles
공학계열 > 건축공학과 > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Song, Young Hak photo

Song, Young Hak
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE