dc.description.abstractThe purpose of this study is to evaluate the ventilation performance of Double Window System in the mixed-use apartment by CFD simulation. The average indoor air speed and PMV are the performance indicators of the study. Indoor air speed and PMV of target building is determined and compared in each case of double window and single window. According to the preliminary analysis of the air flow transmission through each window system in the pressure difference of 10 Pa, double window system shows the larger range of airflow than the conventional project type window system. When the double window system implemented to the mixed-use apartment, indoor air speed increased to 127% in the maximum ventilation mode. In minimum ventilation mode, indoor air speed is 67% of project window system. In the respect of thermal comfort, PMV slightly reduced by 0 ~ 0.2 with the increased air flow speed by the application of double window system. These results indicate the restricted usefulness of the double window system in the respect of the occupants’ thermal perception.-
dc.format.extent10-
dc.language한국어-
dc.language.isoKOR-
dc.publisher대한건축학회-
dc.title이중창호 시스템이 적용된 주상복합건물의 실내 기류특징 분석-
dc.title.alternativeIndoor Air Flow Pattern in the Mixed-Use Apartment with Double Window System-
dc.typeArticle-
dc.publisher.location대한민국-
dc.identifier.bibliographicCitation대한건축학회논문집, v.29, no.12, pp 287 - 296-
dc.citation.title대한건축학회논문집-
dc.citation.volume29-
dc.citation.number12-
dc.citation.startPage287-
dc.citation.endPage296-
dc.identifier.kciidART001829813-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClasskci-
dc.subject.keywordAuthorDouble window system-
dc.subject.keywordAuthorMix-use apartment-
dc.subject.keywordAuthorNatural ventilation-
dc.subject.keywordAuthorCFD-
dc.subject.keywordAuthorPMV-
dc.subject.keywordAuthor이중창호 시스템-
dc.subject.keywordAuthor주상복합건물-
dc.subject.keywordAuthor자연환기-
dc.subject.keywordAuthor전산유체역학-
dc.subject.keywordAuthorPMV-
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Cheong, Chang Heon photo

Cheong, Chang Heon
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE