Cited 0 time in
실험적 방법에 의한 ICT 파이어 댐퍼의 내화성능연구
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 허남수 | - |
| dc.contributor.author | 김인환 | - |
| dc.contributor.author | 장성철 | - |
| dc.contributor.author | 김재웅 | - |
| dc.date.accessioned | 2022-12-26T23:21:07Z | - |
| dc.date.available | 2022-12-26T23:21:07Z | - |
| dc.date.issued | 2014 | - |
| dc.identifier.issn | 1598-6721 | - |
| dc.identifier.issn | 2288-0771 | - |
| dc.identifier.uri | https://scholarworks.gnu.ac.kr/handle/sw.gnu/19299 | - |
| dc.description.abstract | In this paper, fire resistance test was carried out to obtain class H-120 thermal insulation of fire dampers according to a hydrocarbon fire conditions. Specimens were fabricated three different types according to the change of the insulation system applied to damper blade and coaming which were measured surface temperature by performing the fire resistance test. As a test result, specimen-1, 2 of an uninsulated damper blade were exceeded thermal insulation acceptance criteria at 21 minutes, 46 minutes respectively, but specimen-3 of an insulated damper blade was satisfied thermal insulation acceptance criteria during 120 minutes. The test results showed that the insulation of the damper blade was an important factor in the fireproof performance of fire dampers concerning the coaming length minimum 500 mm on the unexposed side as specified test standard. | - |
| dc.format.extent | 8 | - |
| dc.language | 한국어 | - |
| dc.language.iso | KOR | - |
| dc.publisher | 한국기계가공학회 | - |
| dc.title | 실험적 방법에 의한 ICT 파이어 댐퍼의 내화성능연구 | - |
| dc.title.alternative | Fireproof Performance Study of ICT Fire Damper by Using Experimentalmethode | - |
| dc.type | Article | - |
| dc.publisher.location | 대한민국 | - |
| dc.identifier.doi | 10.14775/ksmpe.2014.13.5.082 | - |
| dc.identifier.bibliographicCitation | 한국기계가공학회지, v.13, no.5, pp 82 - 89 | - |
| dc.citation.title | 한국기계가공학회지 | - |
| dc.citation.volume | 13 | - |
| dc.citation.number | 5 | - |
| dc.citation.startPage | 82 | - |
| dc.citation.endPage | 89 | - |
| dc.identifier.kciid | ART001928008 | - |
| dc.description.isOpenAccess | Y | - |
| dc.description.journalRegisteredClass | kci | - |
| dc.subject.keywordAuthor | Fire Damper(방화댐퍼) | - |
| dc.subject.keywordAuthor | Hydrocarbon Fire Resistance Test(탄화수소화재시험) | - |
| dc.subject.keywordAuthor | ICT(정보통신기술) | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
Gyeongsang National University Central Library, 501, Jinju-daero, Jinju-si, Gyeongsangnam-do, 52828, Republic of Korea+82-55-772-0532
COPYRIGHT 2022 GYEONGSANG NATIONAL UNIVERSITY LIBRARY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.