Cited 0 time in
미분무 시스템이 장착된 화염방지장치의 화재 진화 특성에 관한 연구
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | 김해지 | - |
| dc.contributor.author | 이경로 | - |
| dc.date.accessioned | 2022-12-26T20:31:44Z | - |
| dc.date.available | 2022-12-26T20:31:44Z | - |
| dc.date.issued | 2016 | - |
| dc.identifier.issn | 1598-6721 | - |
| dc.identifier.issn | 2288-0771 | - |
| dc.identifier.uri | https://scholarworks.gnu.ac.kr/handle/sw.gnu/15802 | - |
| dc.description.abstract | In this paper, we developed a breather valve with a water mist system for use near an oil storage tank. Ourprocess applied a water mist system to the flame arrester to evaluate the fire suppression characteristics. For thefire suppression evaluation of the water mist system, we evaluated the angle of the nozzle, fire suppression,spray particle size, flashback, fire suppression time, and fire suppression test of antifreeze. Through the firesuppression test, the best fire suppression nozzle used an angle of 140 °, and the flashback phenomenon offlame arrester did not occur. The fire suppression time of water mist system time was within three seconds, andthe antifreeze was no problem with the fire suppression. | - |
| dc.format.extent | 8 | - |
| dc.language | 한국어 | - |
| dc.language.iso | KOR | - |
| dc.publisher | 한국기계가공학회 | - |
| dc.title | 미분무 시스템이 장착된 화염방지장치의 화재 진화 특성에 관한 연구 | - |
| dc.title.alternative | A Study on the Fire Suppression Characteristics of a Flame Arrester with Water Mist System | - |
| dc.type | Article | - |
| dc.publisher.location | 대한민국 | - |
| dc.identifier.doi | 10.14775/ksmpe.2016.15.5.117 | - |
| dc.identifier.bibliographicCitation | 한국기계가공학회지, v.15, no.5, pp 117 - 124 | - |
| dc.citation.title | 한국기계가공학회지 | - |
| dc.citation.volume | 15 | - |
| dc.citation.number | 5 | - |
| dc.citation.startPage | 117 | - |
| dc.citation.endPage | 124 | - |
| dc.identifier.kciid | ART002158496 | - |
| dc.description.isOpenAccess | Y | - |
| dc.description.journalRegisteredClass | kci | - |
| dc.subject.keywordAuthor | Flame Arrester(화염방지장치) | - |
| dc.subject.keywordAuthor | Water Mist System(미분무시스템) | - |
| dc.subject.keywordAuthor | Fire Suppression(화재진화) | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
Gyeongsang National University Central Library, 501, Jinju-daero, Jinju-si, Gyeongsangnam-do, 52828, Republic of Korea+82-55-772-0532
COPYRIGHT 2022 GYEONGSANG NATIONAL UNIVERSITY LIBRARY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.