Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Operation Results and Utility of Dynamic Pricing Response Control-Applied VRF System in Summer Season

Full metadata record
DC Field Value Language
dc.contributor.author김민석-
dc.contributor.author이제헌-
dc.contributor.author송영학-
dc.date.accessioned2022-12-26T19:17:59Z-
dc.date.available2022-12-26T19:17:59Z-
dc.date.issued2017-
dc.identifier.issn1229-6163-
dc.identifier.issn2383-5575-
dc.identifier.urihttps://scholarworks.gnu.ac.kr/handle/sw.gnu/14438-
dc.description.abstractDynamic pricing refers to a system in which a tariff varies, according to a level of charging and applied time depending on time change. The power billing system used in the Korean Electric Power Corporation (KEPCO) is based on time of use (TOU) pricing, which is one of the dynamic pricing systems. This paper aimed to determine the operational results of a variable refrigerant flow system, to which a new control algorithm was applied, in order to respond to dynamic pricing, in summer and the utility of the new control. To do this, real measured data was acquired from a VRF system installed in a building for educational purposes, where dynamic pricing was applied for about 100 days during summer time. At the maximum load operation time period in TOU, the new control minimized operation within the indoor comfort range, an increase in refrigerant evaporation temperature in the indoor unit and the number of revolutions in a compressor in the outdoor unit was limited. As a result, power usage was decreased by 11%, and the operational cost by 14.6%. Furthermore, measurement results using the Predicted Mean Vote (PMV) model, that represented satisfaction of thermal environment, showed that 82.8% to 90.4% of the occupants of the building were satisfied during operation when the new control was applied.-
dc.format.extent7-
dc.language영어-
dc.language.isoENG-
dc.publisher대한건축학회-
dc.titleOperation Results and Utility of Dynamic Pricing Response Control-Applied VRF System in Summer Season-
dc.title.alternativeOperation Results and Utility of Dynamic Pricing Response Control-Applied VRF System in Summer Season-
dc.typeArticle-
dc.publisher.location대한민국-
dc.identifier.doi10.5659/AIKAR.2017.19.3.71-
dc.identifier.bibliographicCitationArchitectural Research, v.19, no.3, pp 71 - 77-
dc.citation.titleArchitectural Research-
dc.citation.volume19-
dc.citation.number3-
dc.citation.startPage71-
dc.citation.endPage77-
dc.identifier.kciidART002266699-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClasskci-
dc.subject.keywordAuthorTOU (Time of Use)-
dc.subject.keywordAuthorVRF system-
dc.subject.keywordAuthorField Measurement-
dc.subject.keywordAuthorEnergy Consumption-
Files in This Item
There are no files associated with this item.
Appears in
Collections
공과대학 > School of Architectural Engineering > Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Song, Young Hak photo

Song, Young Hak
공과대학 (건축공학부)
Read more

Altmetrics

Total Views & Downloads

BROWSE