Cited 0 time in
Experimental study on Venturi-type natural ventilator
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | Kim, Yeong Sik | - |
| dc.contributor.author | Han, Dong Hun | - |
| dc.contributor.author | Chung, Hanshik | - |
| dc.contributor.author | Jeong, Hyomin | - |
| dc.contributor.author | Choi, Soon-Ho | - |
| dc.date.accessioned | 2022-12-26T18:48:46Z | - |
| dc.date.available | 2022-12-26T18:48:46Z | - |
| dc.date.issued | 2017-03-15 | - |
| dc.identifier.issn | 0378-7788 | - |
| dc.identifier.issn | 1872-6178 | - |
| dc.identifier.uri | https://scholarworks.gnu.ac.kr/handle/sw.gnu/13817 | - |
| dc.description.abstract | With the vigorous spread of renewable energy, much attention has been paid to natural ventilation. The natural ventilator is usually classified into a passive type and an active type. Iri this study, the Venturi type ventilator, which is one of the passive type and basically operated by the Bernoulli's principle, was experimentally investigated to evaluate the ventilation characteristics according to the outdoor wind velocities and the opening area of a wall. It was confirmed from the experimental results that the ventilation rate of the Venturi-type ventilator was linearly increased and that the ventilation rate was affected by an intake opening area. The wider the intake opening size gets, the more the ventilation rate increases. Furthermore, the new coefficient of a, which reflects the pressure loss from the intake opening to the mixing zone of the Venturi-type ventilator was introduced and experimentally evaluated. The value of beta, which was evaluated as about 0.08, provides the simple calculation means to estimate the ventilation rate through the Venturi-type ventilator only if the geometric dimensions are known. (C) 2017 Elsevier B.V. All rights reserved. | - |
| dc.format.extent | 10 | - |
| dc.language | 영어 | - |
| dc.language.iso | ENG | - |
| dc.publisher | ELSEVIER SCIENCE SA | - |
| dc.title | Experimental study on Venturi-type natural ventilator | - |
| dc.type | Article | - |
| dc.publisher.location | 스위스 | - |
| dc.identifier.doi | 10.1016/j.enbuild.2017.01.016 | - |
| dc.identifier.wosid | 000395599200023 | - |
| dc.identifier.bibliographicCitation | ENERGY AND BUILDINGS, v.139, pp 232 - 241 | - |
| dc.citation.title | ENERGY AND BUILDINGS | - |
| dc.citation.volume | 139 | - |
| dc.citation.startPage | 232 | - |
| dc.citation.endPage | 241 | - |
| dc.type.docType | Article | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | scie | - |
| dc.description.journalRegisteredClass | scopus | - |
| dc.relation.journalResearchArea | Construction & Building Technology | - |
| dc.relation.journalResearchArea | Energy & Fuels | - |
| dc.relation.journalResearchArea | Engineering | - |
| dc.relation.journalWebOfScienceCategory | Construction & Building Technology | - |
| dc.relation.journalWebOfScienceCategory | Energy & Fuels | - |
| dc.relation.journalWebOfScienceCategory | Engineering, Civil | - |
| dc.subject.keywordPlus | FLUID-MECHANICS | - |
| dc.subject.keywordPlus | ENERGY | - |
| dc.subject.keywordPlus | ASSOCIATION | - |
| dc.subject.keywordPlus | BUOYANCY | - |
| dc.subject.keywordPlus | QUALITY | - |
| dc.subject.keywordAuthor | Bernoulli's equation | - |
| dc.subject.keywordAuthor | Natural ventilation | - |
| dc.subject.keywordAuthor | Reverse flow | - |
| dc.subject.keywordAuthor | Venturi type ventilator | - |
| dc.subject.keywordAuthor | Wind velocity | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
Gyeongsang National University Central Library, 501, Jinju-daero, Jinju-si, Gyeongsangnam-do, 52828, Republic of Korea+82-55-772-0532
COPYRIGHT 2022 GYEONGSANG NATIONAL UNIVERSITY LIBRARY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.