Field test and simulation evaluation of variable refrigerant flow systems performance
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | Lee, Je Hyeon | - |
| dc.contributor.author | Im, Piljae | - |
| dc.contributor.author | Song, Young-hak | - |
| dc.date.accessioned | 2022-12-26T17:17:46Z | - |
| dc.date.available | 2022-12-26T17:17:46Z | - |
| dc.date.issued | 2018-01-01 | - |
| dc.identifier.issn | 0378-7788 | - |
| dc.identifier.issn | 1872-6178 | - |
| dc.identifier.uri | https://scholarworks.gnu.ac.kr/handle/sw.gnu/11994 | - |
| dc.description.abstract | This study aims to compare a performance of Variable Refrigerant Flow (VRF) system with Roof Top Unit (RTU) variable-air-volume (VAV) system through field tests and energy simulations. The field test was conducted at the same conditions as much as possible between two systems such as the installation and operating environments of heating, ventilation and air conditioning (HVAC) system including internal heat gain and outdoor conditions including buildings to compare the performance of two systems accurately. A VRF system and RTU were installed at the test building located in Tennessee Oak Ridge in the USA and the same internal heat gain was generated at the same operating time of the two systems using lighting, electric heater, and humidifier inside the building. The HVAC system was alternately operated between cooling and heating operations to acquire energy performance data and compare energy usage. Furthermore, an hourly building energy simulation model was developed with regard to the VRF system and RTU and then the model was calibrated using actual measured data. Then, annual energy consumptions of the two systems were compared and analyzed using the calibrated model. Moreover, additional analysis was conducted also when the control of discharge air temperature in the RTU was changed. The field test result showed that when energy consumptions of two systems were compared at the same outdoor conditions using the weather-normalized model, the VRF system exhibited energy reduction by 17% during cooling operation and by 74% during heating operation approximately. A comparison on the annual energy consumption using simulations showed that the VRF system reduced more energy consumption than that of the RTU by 60%. When a discharge air temperature in the RTU was controlled according to an outdoor air temperature, energy consumption of RTU was reduced by 6% in cooling temperature and 18% in heating operation, respectively. As a result, energy consumption of the VRF system was reduced more than that of the RTU by 55% approximately. (C) 2017 Elsevier B.V. All rights reserved. | - |
| dc.format.extent | 9 | - |
| dc.language | 영어 | - |
| dc.language.iso | ENG | - |
| dc.publisher | ELSEVIER SCIENCE SA | - |
| dc.title | Field test and simulation evaluation of variable refrigerant flow systems performance | - |
| dc.type | Article | - |
| dc.publisher.location | 스위스 | - |
| dc.identifier.doi | 10.1016/j.enbuild.2017.10.077 | - |
| dc.identifier.scopusid | 2-s2.0-85034666571 | - |
| dc.identifier.wosid | 000428010300017 | - |
| dc.identifier.bibliographicCitation | ENERGY AND BUILDINGS, v.158, pp 1161 - 1169 | - |
| dc.citation.title | ENERGY AND BUILDINGS | - |
| dc.citation.volume | 158 | - |
| dc.citation.startPage | 1161 | - |
| dc.citation.endPage | 1169 | - |
| dc.type.docType | Article | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | scie | - |
| dc.description.journalRegisteredClass | scopus | - |
| dc.relation.journalResearchArea | Construction & Building Technology | - |
| dc.relation.journalResearchArea | Energy & Fuels | - |
| dc.relation.journalResearchArea | Engineering | - |
| dc.relation.journalWebOfScienceCategory | Construction & Building Technology | - |
| dc.relation.journalWebOfScienceCategory | Energy & Fuels | - |
| dc.relation.journalWebOfScienceCategory | Engineering, Civil | - |
| dc.subject.keywordPlus | AIR-CONDITIONING SYSTEM | - |
| dc.subject.keywordPlus | EVAPORATING TEMPERATURE | - |
| dc.subject.keywordPlus | COOLING CONDITIONS | - |
| dc.subject.keywordPlus | ENERGY SIMULATION | - |
| dc.subject.keywordAuthor | Variable refrigerant flow system | - |
| dc.subject.keywordAuthor | Roof top unit | - |
| dc.subject.keywordAuthor | Field test | - |
| dc.subject.keywordAuthor | Simulation | - |
| dc.subject.keywordAuthor | Annual energy performance | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
Gyeongsang National University Central Library, 501, Jinju-daero, Jinju-si, Gyeongsangnam-do, 52828, Republic of Korea+82-55-772-0532
COPYRIGHT 2022 GYEONGSANG NATIONAL UNIVERSITY LIBRARY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.