A Study on verification of changes in performance of a water-cooled VRF system with control change based on measuring data
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | Lee, Je Hyeon | - |
| dc.contributor.author | Kim, Hyemi | - |
| dc.contributor.author | Song, Young-hak | - |
| dc.date.accessioned | 2022-12-26T17:17:44Z | - |
| dc.date.available | 2022-12-26T17:17:44Z | - |
| dc.date.issued | 2018-01-01 | - |
| dc.identifier.issn | 0378-7788 | - |
| dc.identifier.issn | 1872-6178 | - |
| dc.identifier.uri | https://scholarworks.gnu.ac.kr/handle/sw.gnu/11990 | - |
| dc.description.abstract | A variable refrigerant flow (VRF) system is convenient to install and manage as well as the operability via occupants is superior compared to a chiller system. Thus, the use of the VRF system has increased in East Asia and Europe in recent years. In particular, a water-cooled VRF system can solve a space problem of installation for outdoor units in existing air-cooled systems. Thus, it can be applicable to large-sized buildings. However, most cooling tower operations are done with the same setup regardless of the changes in outdoor conditions during the operating period, which is a conservative method for a water-cooled mode. The present study aims to improve the performance of outdoor units in the VRF by reducing the temperature of cooling water to a lower temperature than the existing setup value and verify this through actual measurements. To do this, a new algorithm for a cooling tower operation was developed and applied to a six-week operation during the summer to analyze the effect of the change in setup value. The result showed that power consumption of the cooling tower system and VRF outdoor unit was reduced by 24% and 5.9%, respectively due to the new setup and the coefficient of performance (COP) of the outdoor unit and system was improved by 7.3% and 12.7%, respectively thereby reducing an operation cost by 11%. (C) 2017 Elsevier B.V. All rights reserved. | - |
| dc.format.extent | 9 | - |
| dc.language | 영어 | - |
| dc.language.iso | ENG | - |
| dc.publisher | ELSEVIER SCIENCE SA | - |
| dc.title | A Study on verification of changes in performance of a water-cooled VRF system with control change based on measuring data | - |
| dc.type | Article | - |
| dc.publisher.location | 스위스 | - |
| dc.identifier.doi | 10.1016/j.enbuild.2017.10.014 | - |
| dc.identifier.scopusid | 2-s2.0-85032877812 | - |
| dc.identifier.wosid | 000423636600061 | - |
| dc.identifier.bibliographicCitation | ENERGY AND BUILDINGS, v.158, pp 712 - 720 | - |
| dc.citation.title | ENERGY AND BUILDINGS | - |
| dc.citation.volume | 158 | - |
| dc.citation.startPage | 712 | - |
| dc.citation.endPage | 720 | - |
| dc.type.docType | Article | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | scie | - |
| dc.description.journalRegisteredClass | scopus | - |
| dc.relation.journalResearchArea | Construction & Building Technology | - |
| dc.relation.journalResearchArea | Energy & Fuels | - |
| dc.relation.journalResearchArea | Engineering | - |
| dc.relation.journalWebOfScienceCategory | Construction & Building Technology | - |
| dc.relation.journalWebOfScienceCategory | Energy & Fuels | - |
| dc.relation.journalWebOfScienceCategory | Engineering, Civil | - |
| dc.subject.keywordAuthor | Variable refrigerant flow (VRF) | - |
| dc.subject.keywordAuthor | Cooling tower | - |
| dc.subject.keywordAuthor | Energy usage | - |
| dc.subject.keywordAuthor | Algorithm | - |
| dc.subject.keywordAuthor | High-efficiency | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
Gyeongsang National University Central Library, 501, Jinju-daero, Jinju-si, Gyeongsangnam-do, 52828, Republic of Korea+82-55-772-0532
COPYRIGHT 2022 GYEONGSANG NATIONAL UNIVERSITY LIBRARY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.